The actual product may differ slightly from the image.

SF6 gas

Measuring device for various decomposition products and gas residues

3-032-R003

Gas type
SF6 

For precise measurement

During the operation of gas insulated switchgear, decomposition products might occur after a breakdown having a negative impact on the gas quality in the circuit breaker as well as on the insulation properties. For this reason the measurement of decomposition products is very important. The measurement can be carried out easily by means of test tubes and plastic bags. The following concentrations can be measured:

 

  • sulphur dioxide SO2: 1 to 500 ppmV
  • hydrogen fluoride HF: 1.5 to 15 ppmV
  • oil mist: 1 to 10 mg / m³ (0.16 to 1.6 ppmmass)

Standard version

  • measuring device for decomposition products with flowmeter and needle valve
  • safety valve
  • mounting for test tubes
  • DILO connecting couplings in DN8 and DN20
  • tube opener
  • connecting piece with connecting hose
  • 2 spare O-rings
  • 2 m long flexible connection
  • transport case
  • operating manual
Learn more

Advantages & functions

  • The device is supplied in a handy plastic case. Gastight couplings DN8 and DN20 are also included in the scope of supply.

Technical data

Measuring principle chemical reaction
Dimensions (W x H x D) 360 x 290 x 165 mm with transport case
Weight 2.4 kg without transport case

Optional accessories

10 pieces test tubes for sulphur dioxide SO2 Type 1/a; measuring range 1 to 25 ppmV Plastic bags with a volume of 1 litre are needed (05-1025-R001) 05-1026-R001
Learn more Add to cart
10 pieces test tubes for sulphur dioxide SO2 Type 20/a; measuring range 20 to 220 ppmV Plastic bags with a volume of 1 litre are needed (05-1025-R001) 05-1026-R002
Learn more Add to cart
10 pieces test tubes for sulphur dioxide SO2 Type 50/b; measuring range 50 to 500 ppmV Plastic bags with a volume of 1 litre are needed (05-1025-R001) 05-1026-R003
Learn more Add to cart
10 pieces test tubes for hydrogen fl uoride HF Type 1.5/b; measuring range 1.5 to 15 ppmV Plastic bags with a volume of 2 litres are needed (05-1025-R002) 05-1026-R010
Learn more Add to cart
10 pieces test tubes for detection of oil mist Type 1/a; measuring range 1 to 10 mg/m3 (0.16 to 1.6 ppmmass) Plastic bags with a volume of 10 litres are needed (05-1025-R004)   05-1026-R015
Learn more Add to cart
10 pieces plastic bags with a volume of 1 litre 05-1025-R001
Learn more Add to cart
10 pieces plastic bags with a volume of 2 litres 05-1025-R002
Learn more Add to cart
3 pieces plastic bags with a volume of 10 litres 05-1025-R004
Learn more Add to cart
Adapter for emptying the discharge gas collecting bag 3-969-R005
Learn more Add to cart