SF6 gas refilling- and evacuating device
Mobile as cylinder cart with wire-braided hoses
3-001-4-R002C
- Gas type
- SF6
- Filling of gas
- 0 - 10 bar
- Evacuation of air
- < 1 mbar
- DILO couplings
- DN8/DN20
- Operating voltage
- 110 - 120 V
- Frequency
- 60 Hz
- Operation
- manual
For evacuation of air and safe refilling of SF6 into gas compartments by overpressure
This device covers two important functions: The integrated vacuum pump allows the evacuation of air down to < 1 mbar so that no air/gas mixture is produced during the subsequent filling process. The use of gastight and selfclosing DILO couplings guarantees emission-free gas handling.
The weight of the gas to be refilled can be conveniently registered (with the 3-001-4-R022 / R122 version) by means of the integrated weighing scales. The weight is indicated on the illuminated display which switches off automatically if the scales are not used for a longer period of time. Thanks to the tare function, the gas can be precisely quantified.
Standard version
- vacuum pump for evacuation of air (16 m³/h [at 50 Hz]; 19m³/h [at 60 Hz]), final vacuum 1 mbar
- pressure reducer for SF6
- SF6 cylinder connection W 21.8 x 1/14"
- gauge 0 to -1,200 mbar
- primary gauge NG63, class 1.6, 0 - 60 bar
- secondary gauge NG100, class 1.0, 0 - 10 bar
- indication units in bar, ps, kPa
- ball valve DN8 with hand wheel
- 6 m long wire-braided hose DN8
- DILO couplings DN8 and DN20
- 3 m long electrical connecting cable
- solid tyre wheels
- paint: anthracite-orange
Advantages & functions
- frame
- hose reel
- couplings can be exchanged without any gas loss
- most common global cylinder connections available as accessories
Technical data
| Ambient temperature | 0 to +45 °C | |
| Operating temperature | 0 to +45 °C | |
| Storage temperature | -20 to +60 °C | |
| Dimensions (W x H x D) | 570 x 1360 x 540 mm | |
| Weight | 63 kg | |
| Operating voltage | 110 - 120 V | |
| Frequency | 60 Hz | |
| Protection class | IP 65 |